NK Technologies DT Transducers (Bipolar, Solid-Core)

SKU
DT-BP-FL
Manufacturer:
NK Technologies
NK Technologies

Key Features:

    Three Jumper Selectable Ranges
  • Reduces inventory
  • Eliminates zero and span pots
    Isolation
  • Output is magnetically isolated from the input for safety
  • Eliminates insertion loss (voltage drop)
    Internal Power Regulation
  • Works well, even with unregulated power
  • Cuts installation costs
    Easy Installation
  • Split-Core design with built-in mounting brackets makes installation a snap
Product Options:
$200.00

Secured and trusted checkout with

'DT' Current Transducers from NK Technologies combine a Hall effect sensor and signal conditioner into a single package for use in DC current applications up to 400A. The DT Series has jumper selectable current input ranges and industry standard 0-20mA, 4-20mA, 0-3VDC, 0-5VDC or 0-10VDC outputs. Available in solid or split-core packages.

NK Technologies DT Series DC Current Transducers, Jumper Selectable Input Ranges, 0 - 5 VDC, 0 - 10 VDC or 4 - 20 mADC Output. (Bipolar Output, Solid-Core)

Output Signal• 0–20 mA, 4–20 mA, 0–5 VDC, 0–10 VDC
• ±10 VDC (Bidirectional models only)
Output Limit• 0–20 mA, 4–20 mA: 23 mA
• 0–5 VDC: 5.75 VDC
• 0–10 VDC: 11.5 VDC
Accuracy• Solid-core: 1% FS
• Split-core: 2% FS
Repeatability1.0% FS
Response Time• Solid-core: 20 ms (to 90% of step change)
• Split-core: 100 ms (to 90% of step change)
Frequency RangeDC
Power Supply• 120 VAC (split-core only)
• 24 VAC/DC, 2 VA max.
Power Consumption2 VA
Loading• 0–20 mA, 4–20 mA: 500 max.
• 0–3 or 5 VDC: 25 KΩ min.
• 0–10 VDC: 50 KΩ min.
Isolation Voltage3 KV (monitored line to output)
Linearity0.75% FS
Current Ranges• Solid-core: 0–200 max.
• Split-core: 0–50 min., 0–400 max.
Sensing Aperture• FL Case: 0.75” (19.1 mm) dia.
• SP Case: 0.85” (21.6 mm) sq.
CaseUL94 V0 Flammability Rated
Environmental-4 to 122°F (-20 to 50°C)
0–95% RH, non-condensing
ListingsUL 508 Industrial Control Equipment
(USA & Canada), CE
Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account

Battery Banks

  • Monitors load current
  • Monitors charging current
  • Verifies operation
  • Transportation

  • Measures traction power or auxiliary loads
  • Electric Heating Elements

  • Faster response than temperature sensors