INOR IsoPAQ-632 Isolation Signal Splitter

SKU
70ISL63200
Manufacturer:
Inor Transmitter
Inor Transmitter

Key Features:

  • Calibrated signal setting via DIP switch
    Input and outputs can be set by using DIP switch – high precision without any further adjustment
  • 4-Port isolation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Extremely slim design
    6.2 mm slim housing for a simple and space saving DIN rail mounting
  • Optional In-Rail-Bus mounting rail connector
    Allows for fast and economical installation
  • Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
  • Maximum reliability
    No maintenance costs
$286.00

Secured and trusted checkout with

Inor’s IsoPAQ-632 Signal Splitter/Repeater is essential for isolation, distribution and conversion of 0/4 … 20 mA, 0/1 … 5 V and 0/2 … 10 V standard signals. It boasts a measuring input that can supply the loop power for 2-wire transmitters.

Auxiliary power can be supplied through the optional In-Rail-Bus connector or through the connections terminals. The front of the unit displays a green LED to monitor the power supply.

Using the DIP switch on the IsoPAQ-632, the input and two isolated outputs can now be easily configured. The calibrated range selection makes the IsoPAQ-632 an efficient choice where no further adjustment is necessary.

Input 
Input signal
(calibrated switchable)
0 … 20 mA,  0 … 10 V,   0 … 5 V
4 … 20 mA,  2 … 10 V,  1 … 5 V
Input resistanceCurrent input: ≤ 35 Ω
Voltage input: ≥ 100 kΩ
OverloadCurrent input: < 50 mA
Voltage input: < 30 V
Transmitter supply Tx16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA)
Output I / Output II 
Output signal
(calibrated switchable)
0 … 20 mA,  0 … 10 V,  0 … 5 V
4 … 20 mA,  2 … 10 V,  1 … 5 V
LoadCurrent output: ≤ 6 V (300 Ω at 20 mA)
Voltage output: ≤ 5 mA (2 kΩ at 10 V)
Linear transmission range–1 … +110 %
Residual ripple< 10 mVrms
General Data 
Transmission error< 0.1 % full scale
Temperature coefficient< 100 ppm/K
Cut-off frequency -3 dB-3 dB 5 kHz
Response time T99150 µs
Test voltage 3 kV AC, 50 Hz, 1 min.
Input against Output 1 against Output 2 against power supply
Working voltage (Basic Insulation)600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1
Protection against electrical shockProtective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperatureOperation
– 25 °C to + 70 °C (– 13 to + 158 °F)
Transport and storage
– 40 °C to + 85 °C (– 40 to + 185 °F)
Power supply24 V DC voltage range 16.8 … 31.2 V DC, approx. 1.4 W
EMCEN 61326-1
Construction62 x 96,5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715
WeightApprox. 70 g