INOR IsoPAQ-21L/-22L 1- & 2-Channel Loop Powered Isolators

SKU
70ISL2
Manufacturer:
Inor Transmitter
Inor Transmitter

Key Features:

  • Input to output galvanic isolation
  • Protection against erroneous measurements due to parasitic voltages or ground loops
  • 1- and 2-channel versions allows for optimal cost efficiency
  • No power supply required
  • Reduced wiring saves installation costs
  • Low voltage drop
  • Input voltage drop of less than 2 V reduces impact on the primary current loop
  • Protective Separation
  • The design and high isolation level (4 kV) provides protection for service personnel and downstream devices against impermissibly high voltage
  • High accuracy
  • Negligible additional measurement errors in the loop
  • High-density DIN-rail mounting
  • 12.5 mm (0.5”) housing combined with very low self heating allows for high density mounting
  • Plug-in screw terminals simplifies installation and maintenance
Product Options:
$255.00

Secured and trusted checkout with

IsoPAQ-21L and IsoPAQ-22L are 1- and 2-channel loop powered isolators used for electrical isolation of 0(4)-20 mA signals to avoid measurement errors due to different voltage potentials or ground loops in an instrument installation.

The isolators need no power supply, which contributes to reduced installation costs compared to isolation transmitters.  The high isolation level of 4 kV provides an effective protection for downstream devices.

The high reliability and the Protective Separation are additional features that ensure a safe system operation.

The 2-channel version, IsoPAQ-22L offers a very cost effective alternative combined with a high-density mounting.

 

Input
Input signal0(4)-20 mA / max. 30 V
Operating current< 20 μA
Voltage drop< 2 V
Overload≤ 100 mA, ≤ 30 V
Output
Output signal0(4)-20 mA / max. 28 V
Response time
(10 to 90 % of end value)
2 ms @ 250 Ω load / 6 ms @ 750 Ω load
Ripple< 0.07 % of measured value, ~100 kHz
General data
Transmission error± 0.1 % of end value
Load error± 0.03 % of measured value / 100 Ω load
Temperature coefficient 1)± 0.0015 %/K of measured value / 100 Ω load
Test voltage4 kV, 50 HzBetween all circuits
Working voltage 2) (Basic Insulation)600 VAC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010 part 1 between all circuits.
Protection against electrical
shock 2)
Protective separation acc. to EN 61140 by reinforced insulation acc. to EN 61010 part 1 up to 300 VAC/DC for overvoltage category II and pollution degree 2 between all circuits.
Ambient temperatureOperation
Transport and storage
-20 to +70 °C (-4 to +158 °F)
-35 to +85 °C (-31 to +185 °F)
EMC 3)EN 61326-1
Construction12.5 mm (0.5”) housing, protection class: IP20
Connection≤ 2.5 mm2, AWG 14
WeightApprox. 100 g

 

1) Average TC in specified operating temperature range
2) As far as relevant the standards and rules mentioned above are considered by development and production of our devices. In addition relevant assembly rules are to be considered by installation of our devices in other equipments. For applications with high working voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent situated devices.
3) Minor deviations possible during interference

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account