DENT Instruments CT-SCL-0600-U 600 Amp Standard Large Split Core Current Transformer - DISCONTINUED

SKU
CT-SCL-0600-U
Manufacturer:
DENT Instruments
DENT Instruments

Key Features:

This Product is DISCONTINUED
Please see the DENT Instruments CT-SCM-0600-U as a Recommended Replacement

  • 600 Amp range
  • Large 2.0” window size
  • Holds a typical accuracy of ±1% (measured from 10% to 130%)
  • Internal precision burden resistor across secondary
  • 333mV output at rated current
  • Core interleaved at joints for accuracy
  • ELITEpro and PowerScout series compatible
  • 8ft twisted pair leads - ferrule terminated
  • Protection during installation with shrouded core blades

Secured and trusted checkout with

As part of their “Large” Split Core series, DENT Instruments has designed the CT-SCL-0600-U 600 Amp Standard Split Core Current Transformer with a 2.0” window size. The CT can be installed over already existent electrical power lines, making installation quicker and safer.


The current transformer works by providing linear output voltage directly proportionate to the input current, while holding a typical accuracy of ±1% (measured from 10% to 130%).Even more, the CT-SCL-0600-U is shunted and has a 33mV output at full scale.


The CT-SCL-0600-U is compatible with both the ELITEpro and PowerScout series. 

Window Size

2.0” (5.1 cm)

Current Range

30 - 780A AC

Output

333 mV at rated current

Ratio Error

<1% at rated current (typical)

Phase Error

<2° at rated current (typical)

ELECTRICAL

Output

333 mV at rated current

Wire Polarity

White = Hi, positive (+)

Black = Low, negative (‐)

Frequency Range

50 to 400 Hz

MECHANICAL

Case Material

Epoxy encapsulated housing

Leads

2.7 M (8’), twisted pair, 20 AWG

Operating Temperature

–20° to 55°C (-4° to 131°F)

SAFETY

Working Voltage

600 VAC Category III

Dielectric Strength

5000 VAC around case

600V rated leads

Safety Standards

Conforms to:

UL STD 61010-1

EN 60044-1

Certified to:

CAN/CSA STD C22.2

No. 61010-1

Write Your Own Review
Only registered users can write reviews. Please Sign in or create an account
  • Performance Verification
  • Energy Management
  • New Technology Assessment
  • Tenant Submetering
  • Building Automation