We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
DENT Instrument’s CT-HSC-050-U 50 Amp Mini Standard Hinged Split Core Current Transformer, is one among DENT’s many top-performing “Mini” CTs. The CT-HSC-050-U hinged split core current transformer provides linear output voltage, directly proportional to the input current. The CT has a 50 Amp range while maintaining a (<0.5%) accuracy.
Physically, the CT-HSC-050-U is idyllic for applications that pose the hassle of limited working space. The compact 0.4” window size is perfectly suited for when space is limited, such as multiple loads metering within a panel board. The current transformer is shunted and can be installed over existing electrical power lines, providing safer working practices.
The CT-HSC-050-U is compatible for use with both the ELITEpro and PowerScout series.
Window Size | 0.4” (10mm) |
Current Range | 0.25 ‐ 80A AC |
Output | 333 mV @ 50 A AC 6.66 mV/A AC |
Ratio Error | <0.5% from 0.25 to 80A AC (typical) |
Phase Error | <1.5° from 1 to 80A AC <2° From 0.25 to 1A AC |
ELECTRICAL | |
Output | 333 mV @ 50 A |
Wire Polarity | White = Hi, positive (+) Black = Low, negative (‐) |
Phasing | Arrow on Case Points |
Orientation | Toward Load |
Frequency Range | 50 to 400 Hz |
MECHANICAL | |
Case Material | White Nylon, UL 94 V‐0 |
Leads | 2.4 M (8’), 600V, 20 gage |
Working Temperature | ‐15 to 60°C (5 to 140°F) |
SAFETY | |
Working Voltage | 600 VAC Category III |
Dielectric Strength | 3520 VAC for 1 minute |
Certifications | Conforms to: UL STD 61010‐1 Certified to: CAN/CSA STD C22.2 No. 61010‐1 |
- • Energy Research
- • Energy Management
- • Demand Metering
- • Submetering
- • Load Surveys
Products In This Series
As low as
Now $82.00As low as
Now $82.00