We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
The AmpFlex® is a flexible AC current probe composed of a flexible sensor and an electronic module. The flexible sensor permits measurements on conductors where standard clamp-on probes cannot be used. Measurement range is 5 to 300A. Output signal is 100mV/A and 10mV/A. Sensor length is 24".
ELECTRICAL SPECIFICATIONS | ||||||||||
Current Range | 30A | 200A | 300A | 300A | 30/300A | 500A | 50/500A | 1000A | 100/1000A | 3000A |
Measurement Range | 5 to 30A | 5 to 200A | 5 to 300A | 5 to 300A | 5 to 300A | 5 to 500A | 5 to 500A | 5 to 1000A | 5 to 1000A | 5 to 3000A |
Output Signal(s) | 100mV/A | 1mV/A | 10mV/A | 1mV/A | 100mV/A 10mV/A | 1mV/A | 10mV/A 1mV/A | 1mV/A | 10mV/A 1mV/A | 1mV/A |
Crest Factor (mid-range) | 3.0 | >10 | 3.0 | >10 | 3.0 | >10 | >10 | 9.0 | 9.0 | 3.0 |
Phase Shift @ 50/60Hz | 1.3° | 0.7° | 0.7° | 0.7° | 1.3° | 0.7° | 0.7° | 0.7° | 0.7° | 0.7° |
Residual Noise | 200mA | 200mA | 200mA | 200mA | 200mA | 200mA | 200mA | 200mA | 200mA | 200mA |
ELECTRICAL SPECIFICATIONS | ||||||||||
Current Range | 300/3000A | 300/3000A | 6000A | 600/6000A | 10,000A | 1000/10,000A | 30,000A | 3000/30,000A | ||
Measurement Range | 5 to 3000A | 5 to 3000A | 5 to 6000A | 5 to 10,000A | 5 to 10,000A | 5 to 10,000A | 5 to 30,000A | 5 to 30,000A | ||
Output Signal(s) | 10mV/A 1mV/A | 3.3mV/A 0.3mV/A | 0.1mV/A | 1mV/A 0.1mV/A | 0.1mV/A | 1mV/A 0.1mV/A | 0.1mV/A | 1mV/A 0.1mV/A | ||
Crest Factor (mid-range) | 3.0 | 3.0 | >10 | >10 | 9.0 | 9.0 | 3.0 | 3.0 | ||
Phase Shift @ 50/60Hz | 0.7° | 0.7° | 0.5° | 0.5° | 0.5° | 0.5° | 0.5° | 0.5° | ||
Residual Noise | 200mA | 200mA | 500mA | 500mA | 500mA | 1A | 1A | 1A |
COMMON SPECIFICATIONS | |
Accuracy | 1% of Reading |
Frequency Range | 10 to 20,000Hz* |
Working Voltage | EN 61010, 1000V Cat.III |
Safety Standards | EN 61010, CE Mark and UL listed (E143005) |
Operating Temperature and %RH | 14° to 131°F (-10° to 55°C) (sensor to 90°C), 10 to 90% RH (@50°C) |
Minimum Bend Radius | 0.75" (19mm) |
Water and Dustproofing | Sensor IP45, Module IP40 |
Battery and Battery Life | 9V Alkaline, approx. 150 hours of continuous use |
Good Battery Indication | Green LED |
Electronic Overload Indication | Red LED |
Output | 3/4 spaced banana plugs, optional banana plug to BNC adaptor available, 6.5 ft (2m) lead from sensor to module |
*Intentionally limited for optimum performance
Write Your Own Review
- • Measuring wide bus bars
- • Measuring crowded circuit breaker panels
- • Measuring around large cable bundles
- • Measuring in any traditional application
- • Measuring around irregular shapes