Simpson 228 Leakage Current Tester
|
Item Number: 40027
Manufacturer: Simpson
Part Number: 40027
Product Options
* denotes required field
NIST Traceable Calibration Certificate*
|
|
Simpson 228 Leakage Current Tester
The 228 detects both AC and DC leakage current and simulates human response at three different levels -- reaction, let-go, and burn hazard. Each Model 228 comes with test leads with alligator clips, manual, and batteries.
Features:
- Detects dangerous AC & DC leakage current present on the conductive surfaces of electrical or electronic equipment
- Designed to meet new IEC, ANSI, and UL guidelines
- Reaction, Let-Go and Unweighted Burn Hazard network measurements
- Battery-powered for maximum portability .
Specifications:
| GENERAL |
Reaction Response Network |
Let-Go Response Network |
Unweighted Burn Hazard Response Network |
| Equivalent Network Component Values: |
Complies with values specified in IEC 990 (Excluding fuse) |
|
Equivalent Measuring Instrument Load: |
1 MOhm - 10pF |
1 MOhm - 62 pF |
1 MOhm - 1 pF |
| Ranges: |
0.3, 1, 3, 10 M.I.U. |
0.3, 1, 3, 10 M.I.U. |
0-100 mA RMS |
| Current Accuracy: |
+/- 2% F.S. @ 60 Hz |
| Meter Measurement Method: |
True RMS |
| Meter Frequency Response: |
(Relative to ANSI C101-1992 or UL-1459 2nd edition) |
| DC to 1 Hz |
Pointer shall track within 5% of peak |
| 2Hz to 19 Hz (Accuracy not supported) |
|
| 20 Hz to 200 Hz |
+/- 2% F.S. |
+/- 2.5% of F.S. |
+/- 2% F.S. |
| 200 KHz to 1 MHz |
+/- 2% F.S. |
+/- 2.5% F.S. |
+/- 5% F.S. |
| Output Sensitivity: |
Full scale meter indication equals 1V RMS (Measured with a 1 MOhm, 12 pF load) |
| Output Accuracy: |
+/- 2% of reading @ 60 Hz |
| Output Frequency Response: |
(Relative to ANSI C101-1992 or UL-1459 2nd edition) |
| DC to 50Hz |
+/- 2% of reading |
| 50 Hz to 100 KHz |
+/- 2.5% of reading |
+2%/-3% of reading |
+/-2% of reading |
| 100 kHz to 1 MHz |
+/- 5% of reading |
| Voltmeter Range: |
0-300 V (AC or DC) |
| Voltmeter Accuracy: DC to 1 Hz |
Pointer shall track within 5% of peak |
| 2Hz to 19 Hz (Accuracy not supported) |
|
| 20 Hz to 1 KHz |
+/- 3% F.S. @ 60 Hz (Add +/- 1% for every additional 100 Hz) |
| Voltmeter Frequency Response: |
DC to 1KHz |
| Power Requirements: |
(2) 9V (NEDA 1604A) batteries |
| Physical: |
7" x 5.25" x 3.125", 2-1/2 lbs (1.4kg), ABS plastic, fused input |
| Enviornmental: |
27 Deg C +/- 2 Deg C, 70% non condensing relative humidity. Outside range derate by 10% per Deg C |
| Maximum Operating Range: |
0 Deg to 40 Deg |
|
|


|
|