Fluke 1507 Insulation Resistance Testers
|
Item Number: Fluke-1507
Manufacturer: Fluke
Part Number: Fluke-1507
Product Options
* denotes required field
Calibration Certificate Options*
|
|
Fluke 1507 Insulation Resistance Tester
Features:
- Insulation test range: 0.01 MOhms to 10 MOhms
- Insulation test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V
- Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio
- Make repetitive tests simple and easy with the 1507's Compare (Pass/Fail) function
- Repetitive or hard-to-reach testing is easy with the remote test probe
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- Auto-discharge of capacitive voltage for added user protection
- AC/DC voltage: 0.1 V to 600 V
- 200 mA Continuity
- Resistance: 0.01 Ohms to 20.00 Ohms
- Save battery power with auto power off
- Read measurements easily with large, backlit display
- CAT IV 600 V overvoltage category rating for added user protection
- Remote probe, test leads, probes and alligator clips included with each tester
- Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
- Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
- One year warranty
Specifications:
|
AC/DC Voltage Measurement
|
| Accuracy
|
Range: 600.0 V
Resolution: 0.1V
50 Hz to 400 Hz +/- (% of Rdg + Digits) +/- (2% +3)
|
| Input impedance
|
3 MOhms (nominal), < 100 pF
|
| Common mode rejection ratio (1 kOhms unbalanced):
|
> 60 dB at dc, 50 or 60 Hz
|
| Overload Protection
|
600 V rms or dc
|
|
Earth bond resistance measurement
|
| Range/Resolution
|
| 20.00 Ohm
|
0.01 Ohm
|
| 200.0 Ohm
|
0.1 Ohm
|
| 2000 Ohm
|
1.0 Ohm
|
| 20.00 kOhm
|
0.01 kOhm
|
|
| Accuracy
|
+/- (1.5% +3)
|
| Overload Protection
|
2 V rms or dc
|
| Open Circuit Test Voltage
|
> 4.0 V, < 8 V
|
| Short circuit current
|
> 200.0 mA
|
|
Insulation specifications
|
| Measurement Range
|
0.01 MOhm to 10 GOhm
|
| Test Voltage
|
50 V, 100 V, 250 V, 500 V, 1000 V
|
| Test Voltage Accuracy
|
+ 20%, -0%
|
| Short Circuit Current
|
1 mA nominal
|
| Auto Discharge
|
Discahrge time <0.5 second for C= 1uF or less
|
| Live Circuit Indicator
|
Inhibit test if terminal voltage > 30 V prior to initialization of test
|
| Maximum Capacitive Load
|
Operable with up to 1 uF load
|
| Measure Accuracy:
|
| 50 V:
|
+/-(3 % + 5)
|
| 100 V:
|
+/-(3 % + 5)
|
| 250 V:
|
+/-(1.5 % + 5)
|
| 500 V:
|
+/-(1.5 % + 5)
|
| 1000 V:
|
+/-(1.5 % + 5) to 2000 MOhm, +/-(10 % + 3) above 2000 MOhm
|
|
|
General Specifications
|
| Maximum Voltage Applied to Any Terminal:
|
600 V ac rms or dc
|
| Storage Temperature
|
-40 C to 60 C (-40 F to 140 F)
|
| Operating Temperature
|
-20 C to 55 C (-4 F to 131 F)
|
| Temperature Coefficient
|
0.05 x (specified accuracy) per C for temperatures < 18 C or > 28C (< 64 F or > 82 F)
|
| Relative Humidity
|
|
|
0 % to 95 % @ 10 C to 30 C (50 F to 86 F)
|
|
|
0 % to 75 % @ 30 C to 40 C (86 F to 104 F)
|
|
|
0 % to 40 % @ 40 C to 55 C (104 F to 131 F)
|
|
| Vibration
|
Random, 2g, 5-500 Hz per MIL-PRF-28800F, Class 2 Instrument
|
| Shock
|
1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)
|
| Electromagnetic compatibility:
|
In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)
|
| Safety
|
Complies with ANSI/ISA 80.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)
|
| Certifications:
|
CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition
|
| Batteries
|
Four AA batteries (NEDA 15A or IEC LR6)
|
| Battery Life
|
| Insulation test use:
|
Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MOhm with a duty cycle of 5 seconds on and 25 seconds off.
|
| Resistance measurements:
|
Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ohm with a duty cycle of 5 seconds on and 25 seconds off.
|
|
| Size
|
5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L)
|
| Weight
|
550 g (1.2 lb)
|
| IP Rating
|
IP40
|
| Altitude
|
Operating: 2000m CAT IV 600 V, 3000 m CAT III 600 V
Non-Operating (Storage): 12,000 m
|
| Over-range capability:
|
110 % of range
|
| Included accessories:
|
TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster, and remote probe
|
|
Our Price: Starting at $60.00
The Seahorse Hurricane Series SE-520 hard case is IP6 certified, watertight, airtight, dustproof, and available in a variety of colors with or without pick and pluck foam.
|