Druck UPS-II-IS Intrinsically Safe Loop Calibrator

Druck UPS-II-IS Intrinsically Safe Loop Calibrator

Our Price: Call (732) 632-6400 For Details
Item Number: UPS-II-IS
Manufacturer: Druck (GE)
Part Number: UPS-II-IS

Product Options

* denotes required field

Calibration Options*

Druck UPS II-IS Intrinsically Safe Loop Calibrator

The Druck UPS II Loop Calibrator is an advanced hand held process calibration tool. The UPS-II can power (24 VDC) and read 2-wire transmitters to perform field calibrations. Output currents are adjustable to a resolution of 10 microamps in both source and transmitter simulation modes.

Fixed Steps:

The calibrator can source or stimulate fixed calibration currents to test or calibrate receivers and to stroke valves. Different current levels are available from the menu.

4-20mA Linear
 4 - 8 - 12 - 16 - 20mA
0-20mA Linear
 0 - 5 - 10 - 15 - 20mA
4-20mA sq.rt (Flow)
 4 - 5 - 8 - 13 - 20mA
0-20mA sq.rt (Flow)
 0 - 1.25 - 5 - 11.25 - 20mA
4-20mA
 3.8 - 4 - 4.2 - 12 - 19 - 20 - 21mA

Output currents can be changed manually or automatically. The time between steps is 10 seconds in the auto-stepping mode. In the valve mode, auto-stepping will be:

Ramping:
The calibrator can source or simulate with high resolution a continuous up/down cycle between 4 and 20mA or 0 and 20mA. The travel time between limits is 60 seconds.

Reading in Percentage:
The calibrator can display readings in percentage of a 4-20mA or 0-20mA span and can also read or simulate dP-transmitters directly in percentage of flow.

Features:

  • Sources and Reads Milliamps
  • Simulates 2-Wire Transmitters
  • Powers and Reads 2-Wire Transmitters
  • Reads and Simulates deltaP Transmitters in % Flow
  • Fixed Calibration Currents
  • Auto-Stepping for Handsfree Calibration
  • Auto-Ramp Cycling for Endurance Tests
  • Fixed Currents for Valve Stroking

Technical Specifications:

Output Range:  0 - 21.00mA
Input Range:  0 - 21.00mA
Accuracy:  0.05% of Range
Resolution:  10mA
Temperature Effect:  0.003%/°C (0.0015%/°F)
Internal Loop Power:  24 VDC Stabilized
External Loop Power:  56 VDC Max
Measurement Input:  12 Ohm Including Fuse
Drive Capability:  900 Ohm
Operating Temperature:  -10°C to 50°C (14°F to 122°F)
Battery Life:  Sources 13 Hrs/Measure: 64 Hrs
Batteries 1.5V:  4 x R6, AA (Penlite)
Loop Mismatch:  Flashes “LOOP”
Low Battery Indication:  Flashes “LOBAT”
Overrange:  Flashes “EEEE”
Reversed Polarity:  Flashes “POL”
Housing:  High-Impact ABS
Dimensions:  3.0” x 5” x 0.83”
Weight:  9 Ozs. Including Batteries

Input Safety Parameters     Output Safety Parameters
Ui: < 30 Volts DC Uo Max Out: 21 Volts DC
Ii: < 215 mA DC Io Max Out: 122 mA DC
Pi: < 1.3 Watt Po Max Out: < 0.64 Watt
Ci: = 5nF Co: < 250 nF
Li: Negligible Lo: = < 2.3 mH