AEMC 502 Clamp On Meter
|
Item Number: 502
Manufacturer: AEMC (Chauvin Arnoux)
Part Number: 2117.66
Product Options
* denotes required field
NIST Traceable Calibration - Clamp On DMM*
|
|
AEMC 502 Clamp On Meter
The Clamp-On Meter Model 501 is a general-purpose professional clamp-on. A strong mechanical case design, quality materials, full ranges and compliance to international safety and quality standards ensure a professional and reliable tool. The Model 501 is a True RMS Clamp On which provides RMS measurements for measuring in non-linear electrical environments.
This clamp-on multimeter is auto-ranging, and provides the user with AAC,VAC, VDC, Ohms, Continuity, as well as a frequency measurement function. The jaw opening for the Model 502 is 1.1" (28mm).
The large and complete 4000-count LCD features comprehensive user interface symbols such as a low battery indicator. It is equipped with a Data Hold function, which freezes the measurement. The Model 501 is compact for comfortable one-handed operation, and the hooked jaw design is easy to maneuver in crowded wiring and breaker panels. The jaw opening for the Model 501 is 1.1" (28mm).
Features:
- Compact size - fits into your pocket
- 400AAC current measurements
- 600VAC/DC volts measurements
- True RMS measurements
- Resistance measurements to 400 Ohm
- Continuity with beeper below 40 Ohm
- Frequency measurements from V and A
- Hold function to "freeze" readings
- Large easy-to-read 4000-count display
- 42-segment bargraph
- Includes test leads and a soft carrying pouch
Applications:
- Industrial, commercial, HVAC and residential troubleshooting
- Power panel, junction box and battery bank monitoring
- Electrical testing and troubleshooting on traditional and non-linear leads,
such as adjustable speed drives and computers
Technical Specifications
|
Models |
502 TRMS |
|
AC Ampheres (Auto Ranging) |
0.05 to 400A RMS |
|
Resolution |
0.01 & 0.1A |
|
Accuracy: 50 to 60 Hz 60 to 500Hz |
1.9% Reading +/- 5 counts 2.5% Reading +/- 5 counts |
|
AC Volts(Auto Ranging) |
0.5 to 600 V RMS |
|
Resolution |
0.1 V & 1 V |
|
Accuracy: 50 to 60Hz 60 to 500Hz |
1.5% Reading +/- 5 counts 1.5% Reading +/- 5 counts |
|
Input Impedance |
1 MW |
|
DC Volts(Auto Ranging) |
0.2 to 600 V |
|
Resolution |
0.1 V & 1 V |
|
Accuracy |
1% Reading +/- 2 counts |
|
Input Impedance |
1 MW |
|
Resistance-Ohms(W) |
0.2 to 400 W |
|
Accuracy |
1% Reading +/- 2 counts |
|
Max. Test Voltage |
1.5 VDC |
|
Continuity (Beeper) |
<40 W |
|
Max Test Voltage |
1.5 VDC |
|
Frequency (Hz) (Auto Ranging) |
|
Current Input |
4 to 10 kHz |
|
Resolution |
1 Hz to 10 Hz |
|
Accuracy |
0.1% Reading +/- 1 count |
|
Min Input Signal |
2 A RMS |
|
Voltage Input |
4 to 400 kHz |
|
Resolution |
1 Hz to 100Hz |
|
Accuracy |
0.1 Reading +/- 1 count |
|
Min Input Signal |
5 V RMS |
|
|


|
|